Inspection #: 691330
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Requested by: Edward Washington 19072442731 ewashington@haakensonelec.com | | HVAC retrofitted equipment including (2) AC split units and (2) VAV boxes on 3rd floor.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/29/2022TransferCorrect Below* 3rd floor VAV boxes.Label indicates a max. current of 16A. Drawings show a 15A, 2-pole breaker. 15A OCPD installed. Engineer needs to investigate and change dwg.
6/29/2022TransferCorrect Below* Refrigerant lines.Violate 110.26(E) dedicated space above MDP and possibly other panels.
6/29/2022TransferCorrect Below* AC units indoor and outdoor.Label disconnects.