Inspection #: 690567
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Please call Tony (907) 632-5565 With 45 minute notice to meet on site. Requested by: Tony Noethlich 9073361258 tn@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/14/2022TransferCorrect Below* carrsareas not inspected yet
3/14/2022TransferCorrect Below* customer serviceverify iso ground on iso receptacles
3/14/2022TransferCorrect Below* starbucksupdate panel schedule
3/14/2022TransferCorrect Below* customer serviceupdate panel schedule
3/14/2022TransferCorrect Below* starbuckstrack lighting requires seismic wiring every 4 feet
3/14/2022TransferCorrect Below* starbucksclose all junction boxes
3/14/2022TransferCorrect Below* starbuckscan lights req 2 seismic wires on opposite corners and 4 screws for spanner brackets
3/14/2022TransferCorrect Below* oaken kegpossibly other items without panel schedule
3/14/2022TransferCorrect Below* oaken kegdisconnects required on each cooler unit- must be grouped
3/14/2022TransferCorrect Below* oaken kegwhere is nameplate on coolers? need to verify UL listing and amperage/voltage ratings for overcurrent protection
3/14/2022TransferCorrect Below* oaken kegseismic wires req at every 4' of track lighting
3/14/2022TransferCorrect Below* oaken kegclose all junction boxes
3/14/2022TransferCorrect Below* oaken keglabel neutrals with circuit numbers
3/14/2022TransferCorrect Below* oaken kegpanel requires ko seals
3/14/2022TransferCorrect Below* oaken kegupdated panel schedule required
3/14/2022TransferCorrect Below* oaken keglabel panel with source