Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 689634
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: Service approved. Tag 37800. Electrical rough approved for 2nd floor east electrical room, and lower framed ceilings in rooms 402 through 420.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/25/2021Transfer01See inspection comments Microturbine-one line diagram, separately derived system. Grounding electrode conductor required.
10/25/2021Transfer01See inspection comments Service, microturbineVerify microturbine configuration with utility. Verify disconnecting means and requirement for having lockable disconnect. Labeling required for alternate source per 702.
10/25/2021Transfer01See inspection comments Service.Label AFC and date calculated.
10/22/2021Transfer01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.
10/22/2021Corrected01See inspection comments Exterior structural steel not connected to interior steel.GEC / bonding connection is required to the steel itself rather to rebar in a footing that supports the steel.
10/22/2021Corrected01See inspection comments Structural steel framework within the building.Structural steel that is completely wrapped in sheetrock or other non-conductive materials is not specifically required to be bonded into the grounding electrode system. If the interior structural steel is to be used as an interconnection between electrodes, it needs to follow connection rules. 250.68(A) Exception 2 refers to "fireproofed" steel connections accessiblility. "Fireproofed" is interpreted to mean foreproof coatings such as monokote.
10/22/2021Corrected01See inspection comments Service raceway bonding.No more than (2) service raceways to be bonded using (1) 3/0 copper bonding conductor..
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter