Inspection #: 686078
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Correction
Comment: 3rd floor guest rooms and electrical room from 327 / 330 to east and south to 350 / 351. Electrical wall and above sheetrock ceiling rough approved. Corrections pertain to service and system grounding and bonding.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/22/2021Transfer01See inspection comments Location of branch circuit panel in pool equipment room. Drawings show panel in pool equipment room.2017 680.14(A) defines a pool equipment room as a corrosive environment and requires specific wiring methods. The pool room itself is also a corrosive environment. The panel will have to be isolated from corrosive atmospheres.
10/22/2021Transfer01See inspection comments Exterior structural steel not connected to interior steel.GEC / bonding connection is required to the steel itself rather to rebar in a footing that supports the steel.
10/22/2021Transfer01See inspection comments Structural steel framework within the building.Structural steel that is completely wrapped in sheetrock or other non-conductive materials is not specifically required to be bonded into the grounding electrode system. If the interior structural steel is to be used as an interconnection between electrodes, it needs to follow connection rules. 250.68(A) Exception 2 refers to "fireproofed" steel connections accessiblility. "Fireproofed" is interpreted to mean foreproof coatings such as monokote.
10/22/2021Transfer01See inspection comments Service raceway bonding.No more than (2) service raceways to be bonded using (1) 3/0 copper bonding conductor..