Inspection #: 682319
Inspection Type: Electrical Rough
Inspector: N.Holland
Result: Partial
Comment: Rough Approved. Note AFCI and GFCI protection required. Tamper resistant type receptacles will need to be installed and weather resistant type on the exterior. With extra Duty type covers on those exterior receptacles.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/13/2021Corrected01See inspection comments ThroughoutNail plates required where romex is within 1 1/4" of face of the stud
9/13/2021Corrected01See inspection comments Through outSecuring and supporting romex. within 12" of boxes and enclosures, and supporting in intervals not exceeding 4 1/2 feet. 2017 NEC 334.30