Date | Status | Code | Description | Ref | Location | Comments |
9/7/2021 | Corrected | PlumbRgh14 | Comments | See Inspectors Comments | | DWV support missing in each room serving the Lav. See section 313 in UPC for support requirements |
9/7/2021 | Corrected | PlumbRgh14 | Comments | See Inspectors Comments | | Hammer arrestors required in each room. Lavs, shower valves and WC |
9/7/2021 | Corrected | PlumbRgh14 | Comments | See Inspectors Comments | | per 707.4 cleanouts required at termination of building sewer. Each waste stack serving rooms above will require an accessible cleanout. |