Inspection #: 679830
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Progress final approved for public area. Electrical final conditionally approved for use until 4/29/22.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/29/2022TransferCorrect Below* Demonstrate overload setting for 4th floor VFD to RF-1. 
3/29/2022TransferCorrect Below* Relocation of circuit to RF-1. Provide field change order for relocation of branch circuit supply.  
3/29/2022TransferCorrect Below* AHU replacement incomplete.  