Inspection #: 675945
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Plumbing Rough - Approved DWV/water rough & tests approved, DWV related to stacks & rm piping serving 108-408, 109-409 & 210-410, water related to rms 104 & 409, OK to cover.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/9/2021TransferPlumbRgh14CommentsSee Inspectors CommentsWater pipingAs per 2021 UPC 609.10 water hammer arrestors required.
8/9/2021CorrectedPlumbRgh4ABS/PVC SupportABS/PVC horizontal piping shall be supported every 4 feet horizontally- UPC Table 313.1Horizontal underfloor lav DWV 