| Date | Status | Code | Description | Ref | Location | Comments |
| 7/12/2022 | Transfer | Correct service item below | * | | Smoke detectors. | Required in each bedroom and CO / smoke detector required in common area. |
| 7/12/2022 | Transfer | Correct service item below | * | | 240V dryer receptacle. | No circuit in panel. |
| 7/12/2022 | Transfer | Correct service item below | * | | Master bedroom ceiling fan. | Verify fan rated box. |
| 7/12/2022 | Transfer | Correct service item below | * | | Replaced receptacles throughout. | Require AFCI protection per NEC 406.4(D). |
| 7/12/2022 | Transfer | Correct service item below | * | | GFCI protection per 2017 NEC. | Laundry, dishwasher, gas range receptacles do not appear to be GFCI. If protecting with a GFCI breaker (not changing receptacle), AFCI protection not required. |
| 7/12/2022 | Transfer | Correct service item below | * | | Conduit chase into panel. | Duct seal. |
| 7/12/2022 | Transfer | Correct service item below | * | | Underground feeder. | Direct burial conductors required to be at least 2ft deep. |
| 7/12/2022 | Transfer | Correct service item below | * | | Under mobile home. | Direct burial feeder conductors, emerging from grade, require at least, coreflow for physical protection. |