Inspection Type: Electrical Service
Inspector: M.Green
Result: Correction
Comment: Please call 1/2 hr prior Requested by: darryl 907-350-5545 drselectric@yahoo.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/12/2022TransferCorrect service item below* Smoke detectors.Required in each bedroom and CO / smoke detector required in common area.
7/12/2022TransferCorrect service item below* 240V dryer receptacle.No circuit in panel.
7/12/2022TransferCorrect service item below* Master bedroom ceiling fan.Verify fan rated box.
7/12/2022TransferCorrect service item below* Replaced receptacles throughout.Require AFCI protection per NEC 406.4(D).
7/12/2022TransferCorrect service item below* GFCI protection per 2017 NEC.Laundry, dishwasher, gas range receptacles do not appear to be GFCI. If protecting with a GFCI breaker (not changing receptacle), AFCI protection not required.
7/12/2022TransferCorrect service item below* Conduit chase into panel.Duct seal.
7/12/2022TransferCorrect service item below* Underground feeder.Direct burial conductors required to be at least 2ft deep.
7/12/2022TransferCorrect service item below* Under mobile home.Direct burial feeder conductors, emerging from grade, require at least, coreflow for physical protection.