Inspection #: 673971
Inspection Type: Plumbing Rough
Inspector: E.Wood
Result: Partial
Comment: Water rough-in and tests for rooms 115 thru 118, Approved. Heat piping and tests for rooms 115, 215, 315, 415, 117, 217, 317, 417, 118, 218, 318, 418, 120, 220, 320, 420, 121, 122, 222, 322, 422, 224, 324, 424, Approved. Condensate piping and tests for rooms 215, 315, 415, 217, 317, 417, 218, 318, 418, 220, 320, 420, 222, 322, 422, 224, 324, 424, Approved. Rain leader and tests for RD's and OD's at grids C x 1.7, F.6 x 1.7, and F.6 X 5, Approved. OK to wrap piping.