Inspection #: 670013
Inspection Type: Mechanical Inspection
Inspector: E.Huckaba
Result: Correction
Comment: Range hood and ducting, bath fan replacement and Rest of Water Heater Replacement- APPROVED. NOTES: VIDEO INSPECTION. PLEASE MAKE CORRECTION AND CALL BACK IN FOR RE-INSPECTION. VIDEO INSPECTION IS ACCEPTABLE.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/4/2021TransferBoiler3Combustion Air RequiredCombustion air required - IFGC 304.1COMBUSTION AIR FOR WATER HEATER.COMBUSTION AIR IS INSTALLED HOWEVER THE PAN IS ON TOP OF THE COBUSTION INTAKE AND NOT ALLOWING FOR ANY AIR FLOW. PER INSTALL GUIDE PAGE 7- THE COMBUSTION AND VENTILATION AIR FLOW MUST NOT BE OBSTRUCTED. PLEASE INSTALL PER INSTALL GUIDE.