Inspection #: 663885
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/27/2021 Correct Below* Salon.EM battery troffer needs lamps to test.
5/27/2021 Correct Below* Existing lighting.Drawings show most lights being replaced. No lights replaced; owner wants to save money. Have engineer send in change order to accept existing lighting.
5/27/2021 Correct Below* Break room.GFCI devices cannot be behind washers and dryers.
5/27/2021 Correct Below* Branch circuit panels.Drawings show approx. 40K available fault current. 10K AIC breakers installed.
5/27/2021 Correct Below* Rooftop EF-1.Not installed at this time.
5/27/2021 Correct Below* Classroom 003 east wall.(4) quad receptacles not installed at this time.