| Date | Status | Code | Description | Ref | Location | Comments |
| 5/27/2021 | | Correct Below | * | | Salon. | EM battery troffer needs lamps to test. |
| 5/27/2021 | | Correct Below | * | | Existing lighting. | Drawings show most lights being replaced. No lights replaced; owner wants to save money. Have engineer send in change order to accept existing lighting. |
| 5/27/2021 | | Correct Below | * | | Break room. | GFCI devices cannot be behind washers and dryers. |
| 5/27/2021 | | Correct Below | * | | Branch circuit panels. | Drawings show approx. 40K available fault current. 10K AIC breakers installed. |
| 5/27/2021 | | Correct Below | * | | Rooftop EF-1. | Not installed at this time. |
| 5/27/2021 | | Correct Below | * | | Classroom 003 east wall. | (4) quad receptacles not installed at this time. |