Date | Status | Code | Description | Ref | Location | Comments |
3/24/2022 | Transfer | Correct Below | * | | Guest rooms motorized shades. | Sheet Note 5 requires a power connection to motorized shades. Are these installed at this time. Will need to verify proper equipment, etc. as part of inspection process. |
3/24/2022 | Transfer | Correct Below | * | | Guest rooms 3-panel screen separating sink from rest of room. | Sheet Note 4 indicates an electrical connection to the screen for LED lighting. Will need to see this installed if electrical equipment. Also, will need to see to determine if GFCI protection is required for receptacle within 6ft. |
3/24/2022 | Transfer | Correct Below | * | | Room 412. | Drawings at MOA do not show this with (2) clothes washers and 240V dryers. Was this a change order? |
3/24/2022 | Transfer | Correct Below | * | | Room 412 washer receptacles. | 210.8 requires all GFCI devices to be installed in a readily accessible location. NOTE: 2017 NEC does not require GFCI protection in non-dwelling unit laundry areas. |
3/24/2022 | Transfer | Correct Below | * | | Room AC units. | Units labelled to require 15A OCPD. |