Inspection #: 654582
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/17/2021TransferCorrect Below*  Provide installation instructions for units.
3/26/2021TransferCorrect Below* North unit- North terminal. Provide installation instructions for unit. Unit shown as max 20 amp overcurrent device. Currently connected through 30 amp circuit, plug and receptacle
3/26/2021TransferCorrect Below* South terminalProvide installation instructions for units-Fixed stationary equipment properly supplied not permitted to be cord and plug connected above 30 amp.
3/25/2021TransferCorrect Below*  Plans show replacing overcurrent protection with 35 amp OCP, 40 amp remains.
3/25/2021TransferCorrect Below* South terminalPanel schedule shows circuit being fed from 031QHA, previous circuit and new circuit fed from 071QHA. Correct plans or locate to panel noted. Provide updated plans with field change order.