Inspection #: 651531
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: CondAppr
Comment: Requested by: Cody dishon 7157486 Patrickm@orionconstructioninc.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/1/2021 Fire 2CCO approvalFire Final approved for CCO CCO approved for setup of the office space till March 15th 2021.  
3/1/2021 Fire 13Correction(s) #1Please correct the following: <div>Training room 123 has an occupant load of 88 occupants and required Emergency lights, exit signs and panic hardware.&nbsp; Architect has the room as an A Occupancy with an occupant load factor or 15 sq.ft per person.&nbsp; &nbsp;If the room is reclassified as it may not required equipment.&nbsp;&nbsp;</div><div><br></div><div>Contractor need to reach out to EIC at0561-5543 for project 19-0033.01</div>
3/1/2021 Fire 15Correction(s) #2Please correct the following: Fire alarm layout is not code compliant for ADA layout for Visable alarm for public use areas and common use areas per 2012/2018 IFC 907.5.2.3.1 and NFPA 72, the wall strobes are obstructed by the cubicles and do not meet the intent of providing visual notification to hearing impairs people.&nbsp; Multiple areas have no strobe coverage.&nbsp; Have a fire alarm system company evaluate, provide design and permit to install compliant coverage.
3/1/2021 Fire 16Correction(s) #3Please correct the following: Unable to test existing exit lights and emergency lighting.&nbsp; Contractor unable to locate breakers.&nbsp; &nbsp;Identify breaks so emergency systems can be tested.