Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 647099
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Trendsetters TI in University Center. Conditional electrical final approved until 6/27/2021 to set up business. Correct items below and request reinspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/27/2021TransferCorrect Below* Salon.EM battery troffer needs lamps to test.
5/27/2021TransferCorrect Below* Existing lighting.Drawings show most lights being replaced. No lights replaced; owner wants to save money. Have engineer send in change order to accept existing lighting.
5/27/2021TransferCorrect Below* Break room.GFCI devices cannot be behind washers and dryers.
5/27/2021TransferCorrect Below* Branch circuit panels.Drawings show approx. 40K available fault current. 10K AIC breakers installed.
5/27/2021TransferCorrect Below* Rooftop EF-1.Not installed at this time.
5/27/2021TransferCorrect Below* Classroom 003 east wall.(4) quad receptacles not installed at this time.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS