Inspection #: 646781
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: CondAppr
Comment: Contact Superintendent upon arrival Jonah 373-8513. Electrical Final is also scheduled for 02/19/21 PM inspection. We are reqeusting a CCO or CO to be in affect on 02/19/21. Requested by: Rachael Ridge 9073173613 RachaelR@OrionConstructionInc.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/19/2021 Fire 15Correction(s) #2Please correct the following: Area B not ready for inspection
2/19/2021 Fire 13Correction(s) #1Please correct the following: Training room 123 has an occupant load of 88 occupants and required Emergency lights, exit signs and panic hardware.&nbsp; Architect has the room as an A Occupancy with an occupant load factor or 15 sq.ft per person.&nbsp; &nbsp;If the room is reclassified as it may not required equipment.&nbsp;&nbsp;<br><div><br></div><div>Contractor need to reach out to EIC at0561-5543 for project 19-0033.01</div>
2/19/2021 Fire 2CCO approvalFire Final approved for CCO CCO Approved for area "A" till March 1, 2021