Inspection #: 645997
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections for final.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/24/2021TransferCorrect Below*  Provide MOA stamped reviewed plans and change orders related to X21-1011 and X20-1784 for inspection.
12/31/2020TransferCorrect Below* Panel EEUnable to locate new connections documented on plans to panel EE while onsite. Update plans to include associated work of not already included.
12/31/2020TransferCorrect Below* Labeling at switchboards and ATS'Verify and update labeling as required on generator switch boards and ATS equipment. Verify power one-line diagrams and associated labeling are accurate and correspond with equipment labeling. Labels required at generators and new load connection for switching procedure.
12/31/2020TransferCorrect Below* PlansProvide complete MOA reviewed electrical plans for inspection to include Change orders X20-1784 and X20-1185
12/31/2020CorrectedCorrect Below* ATS -03 and ATS -12 Reduced working clearances remains from previous inspections.