Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 644803
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Corrections remain.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/31/2020TransferCorrect Below* Panel EEUnable to locate new connections documented on plans to panel EE while onsite. Update plans to include associated work of not already included.
12/31/2020TransferCorrect Below* Labeling at switchboards and ATS'Verify and update labeling as required on generator switch boards and ATS equipment. Verify power one-line diagrams and associated labeling are accurate and correspond with equipment labeling. Labels required at generators and new load connection for switching procedure.
12/31/2020TransferCorrect Below* PlansProvide complete MOA reviewed electrical plans for inspection to include Change orders X20-1784 and X20-1185
12/31/2020TransferCorrect Below* ATS -03 and ATS -12 Reduced working clearances remains from previous inspections.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS