| Date | Status | Code | Description | Ref | Location | Comments |
| 12/23/2020 | Corrected | Correct Below | * | | Boiler room disconnect switch boxes. | Class 2 wiring cannot enter this box to connect to donut CT device; separation between class 1 and class 2 wiring cannot be maintained. Suggest putting CT in separate box with only the loop of wire needed to run through the donut. Class 2 wiring will need to enter through another opening and maintain 1/4 inch separation. |
| 12/23/2020 | Corrected | Correct Below | * | | Above T-bar grid in south end office area. | AC compressor requires disconnect. Have drawings on site that show this change order. |