| Date | Status | Code | Description | Ref | Location | Comments |
| 3/26/2021 | Transfer | Correct Below | * | | North unit. | Provide installation instructions for unit. Unit shown as max 20 amp overcurrent device. Currently connected through 30 amp circuit, plug and receptacle |
| 3/26/2021 | Transfer | Correct Below | * | | South terminal | Provide installation instructions for units-Fixed stationary equipment properly supplied not permitted to be cord and plug connected above 30 amp. See 660.4(A) |
| 3/25/2021 | Transfer | Correct Below | * | | | Plans show replacing overcurrent protection with 35 amp OCP, 40 amp remains. |
| 3/25/2021 | Transfer | Correct Below | * | | South terminal | Panel schedule shows circuit being fed from 031QHA, previous circuit and new circuit fed from 071QHA. Correct plans or locate to panel noted. |