Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/26/2021TransferCorrect Below* North unit. Provide installation instructions for unit. Unit shown as max 20 amp overcurrent device. Currently connected through 30 amp circuit, plug and receptacle
3/26/2021TransferCorrect Below* South terminalProvide installation instructions for units-Fixed stationary equipment properly supplied not permitted to be cord and plug connected above 30 amp. See 660.4(A)
3/25/2021TransferCorrect Below*  Plans show replacing overcurrent protection with 35 amp OCP, 40 amp remains.
3/25/2021TransferCorrect Below* South terminalPanel schedule shows circuit being fed from 031QHA, previous circuit and new circuit fed from 071QHA. Correct plans or locate to panel noted.