Click Here To View Another Inspection


Inspection #: 636486
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: After hours 9th floor fire inspection. Wednesday 10-21-20 Requested by: John Ryan 19079521146 jryan@aknss.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/23/2020Transferfirealarm13Please correct the followingPlease correct the following: Provide change order for solution to low decibel's in office areas with no speakers.
10/23/2020Transferfirealarm3Decibel reportProvide Decibel Level Report. Provide decibel report for all glass offices that do not have speakers installed in them on floors 4, 9 and 12.&nbsp; During testing of the 9th floor several offices did not meet the minimum 60 dBA on the alert tone as required by local amendment 23.45.907.5.2.1.1.&nbsp; &nbsp;<div><br></div><div>During the test 2 to 3 speakers were taken from 1/2 watt to 2 watts to make 60 dBA in the office, but it caused the amplifier to be over loaded.&nbsp; Designer and building owner need to evaluate on adding speakers to offices or adding additional amplifiers to allow for speaker wattage to be increased. Note: increased wattage may cause a decrease in voice intelligibility.&nbsp;&nbsp;</div>
10/23/2020Transferfirealarm2Install cert <p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p>  Provide fire alarm install certification
10/23/2020Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO CCO approved for floors 4, 9 and 12 fire alarm till December 31, 2020