Inspection #: 630370
Inspection Type: Temp Electric
Inspector: N.Holland
Result: Partial
Comment: Rough in walls inspection. Approved for classroom 003 and 007, except hair wash station in 003. See Corrections for notes

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/25/2021TransferCorrect following Item  Prints NotePrints show it will be a series combination system. See 2017 NEC 240.86 (B). Proper labeling 2017 NEC 110.22 (C). Provide a cut sheet of breakers installed with series ratings label that the types match up for the series rating.