Inspection #: 629712
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Final Electrical Please call Steve 1 hour ahead if possible. 907-355-7834 2049 UAA UC Boiler Replacement Requested by: Samantha Stanley 9073763301 reception@mechsp.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/23/2020TransferCorrect Below* Boiler room disconnect switch boxes.Class 2 wiring cannot enter this box to connect to donut CT device; separation between class 1 and class 2 wiring cannot be maintained. Suggest putting CT in separate box with only the loop of wire needed to run through the donut. Class 2 wiring will need to enter through another opening and maintain 1/4 inch separation.
12/23/2020TransferCorrect Below* Above T-bar grid in south end office area.AC compressor requires disconnect. Have drawings on site that show this change order.