| 1/8/2021 | | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | Fire alarm system is approved for CCO till January 22, 2021 |
| 1/8/2021 | Transfer | Firealarm15 | Correction(s) #2 | <div>Correct the following item(s):</div><div><br></div> | | Message beds shall shut down when running they produce approximately 85 dBA which above the sound output of the fire alarm speakers to be 15 dba over ambient sound 2012 IFC 907.58.2.1.1. This additionally makes the voice evacuation system unintelligible and is out of compliance with NFPA 72 for a voice evac system. |
| 1/8/2021 | Transfer | Firealarm14 | Correction(s) #1 | <div>Correct the following item(s):</div><div><br></div> | | Locker room speakers need to be increased in dBA. |