Inspection #: 629509
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: Bart, Hoping to meet at 8:30am as we planned. Thanks! Requested by: brandon engelbracht 9073600035 Brandon@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/8/2021 firealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire alarm system is approved for CCO till January 22, 2021
1/8/2021TransferFirealarm15Correction(s) #2<div>Correct the following item(s):</div><div><br></div> Message beds shall shut down when running they produce approximately 85 dBA which above the sound output of the fire alarm speakers to be 15 dba over ambient sound 2012 IFC 907.58.2.1.1.&nbsp; &nbsp;This additionally makes the voice evacuation system unintelligible and is out of compliance with NFPA 72 for a voice evac system.
1/8/2021TransferFirealarm14Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Locker room speakers need to be increased in dBA.