Inspection #: 625487
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Approved
Comment: Electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/18/2020CorrectedCorrect Below* Gate control cabinet. Label requires 20 amp rated supply circuit. 40 amp currently installed.
7/8/2020CorrectedCorrect Below* Panel schedules.Label spare breakers. Verify labelling of panel source of supply.
7/8/2020CorrectedCorrect Below* Underground j-box metal lid by transformer and panel H-frame.Bonding strap not properly connected to grounding system in box. Use Copper C.