Click Here To View Another Inspection Inspection #: 624109 Inspection Type: Roof Nailing Inspector: H.Kahlstrom Result: Approved Comment: West High 8-10-20 Within the grid confines between B.5 to C.9 and 4.6 to 5.2 on J roof observed the following. 1/2” plywood sheathing attachment with .148x 2-3/8” galvanized Grip Rite nails. Nailing pattern is 6” on center in the field and 2” on center at perimeter panel edges. Sheathing was installed with a 4’ stagger between edge seams. CMSTC16 strapping was Installed on a 6’ spacing each way attached with .148 x 1-1/2” galvanized Grip Rite nails in each hole. All CMSTC16 field splices were 14” or greater. The north end termination was detail 2/S5.1. At 2 locations on the east and west ends termination was detail 5/S5.1 and consisted of a MTSD5 marriage strap that attached to a HTT5 tension tie anchored to the concrete curb with a 5/8” x 8” A-307 galvanized threaded rod which was epoxied with Hilti HIT RE 500V-3 (expiration 1-21) with 6-1/2” deep prepared holes utilizing the Hilti vacuum. Inspection Corrections DateStatusCodeDescriptionRefLocationComments