Inspection #: 621407
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: This inspection created because 7/21/2020 inspection was requested in error as an electrical rough instead of an electrical final. Conditional electrical final approved until 8/21/2020 to resolve remaining item below. OK for tenant to move in and begin business. No site visit required for this inspection.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/23/2020TransferCorrect Below* Existing panels Mech 1 and Mech 2.Drawings show 20KA + available fault current. 10K breakers installed. Engineer's email states that panel Mech 2 motor load will permit series rating. Email indicates that panel Mech 1 does not meet NEC 240.86 criteria for series rating due to motor load. Available fault current at Mech 1 needs to be resolved.