| Date | Status | Code | Description | Ref | Location | Comments |
| 7/20/2020 | Corrected | Correct Below | * | | Upstairs panels Mech 1 and Mech 2 existing condition. | Panels above are shown on drawings as having available fault current of over 20KA. 10K branch circuit breakers installed. Breakers may not series rate because of motor loads in panels. Engineer needs to investigate. |
| 7/20/2020 | Corrected | Correct Below | * | | Panel 1LS | Correct panel schedules, post floor plan for office furniture. |
| 7/20/2020 | Corrected | Correct Below | * | | Panel 1LS | 3-pole breakers or handle ties required for office furniture multi-wire branch circuits. |