Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 620745
Inspection Type: Final Electrical
Inspector: M.Green
Result: Approved
Comment: 22K breakers installed in panel Mech 1. TI electrical final approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/20/2020CorrectedCorrect Below* Upstairs panels Mech 1 and Mech 2 existing condition.Panels above are shown on drawings as having available fault current of over 20KA. 10K branch circuit breakers installed. Breakers may not series rate because of motor loads in panels. Engineer needs to investigate.
7/20/2020CorrectedCorrect Below* Panel 1LSCorrect panel schedules, post floor plan for office furniture.
7/20/2020CorrectedCorrect Below* Panel 1LS 3-pole breakers or handle ties required for office furniture multi-wire branch circuits.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS