Inspection #: 618283
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/13/2020TransferCorrect Below* MDPCorrection remains for AFC: Submit updated calculated Fault currents to MOA plan review for approval. Eaton type BAB-H breakers shown to be approved for use with feeder overcurrent protection used to achieve series ratings. Branch circuit OCPD's used are type BA and not BAB-H. BA type circuit breakers appear in catalog to be used as special purpose. BA type breakers do not appear to be type approved for use with series ratings per the documentation provided onsite. Eaton technical engineer or project electrical engineer of record required to address and provide documentation.