Inspection #: 617844
Inspection Type: Final Electrical
Inspector: M.Green
Result: Partial
Comment: Many items corrected. Several items still require resolution. Conditional electrical final approved until 7/15/2020 to resolve uncorrected issues below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/29/2020TransferCorrect Below* MDPLabeling for the series ratings. 2017 NEC 240.86 (A) (B). 110.22 (C)
6/29/2020TransferCorrect Below* Service and MDPAvailable fault current at service calculated at 68,780A. Unresolved AFC issues as follows: 1. Architect emailed a fault current schedule that appears to show 66KA + available fault current at the MDP - THIS EXCEEDS THE 65K RATING OF THE MDP BREAKERS. 2. MDP section breakers are Eaton types ED, FD, HFD 65K rated. Branch circuit panel breakers are Eaton type BA @ 10K rating. Could not find any reference to Eaton type BA breakers series rating with the feeder breaker types installed (even if fault current is less than 65K at MDP). 3. Engineer needs to verify available fault current calculations at RTUs. 4. Any solution (such as AFC recalculation or switchgear modification) is required to be submitted to MOA plan review for approval.
6/29/2020TransferCorrect Below* Front and Central Cashier areasDoes not appear to be a listed system for the following reasons: 1. Isolated ground receptacles not connected to an isolated ground. 2. Cord and plug used to connect permanent wiring.
6/29/2020CorrectedCorrect Below* SE corner, Front, Central areasReceptacles have no power
6/29/2020CorrectedCorrect Below* RooftopExhaust fan on rooftop does not have a disconnect in line of sight.
6/29/2020CorrectedCorrect Below* Back storage area and loading dockEmergency lights not working
6/29/2020CorrectedCorrect Below* Back Hallway near restroomsExit signs not working, and emergency light outside exit door.
6/29/2020CorrectedCorrect Below* Break roomGFI protection required for receptacles within 6 ft of the sink.
6/29/2020CorrectedCorrect Below* Loading dockInstall a box, and cover plates, for security lighting.
6/29/2020CorrectedCorrect Below* GutterNorth End of Gutter appears to have more than 30 current carrying conductors. 2017 NEC 366.22 (A)
6/29/2020CorrectedCorrect Below* MDPInstall panel schedules, Label for RTU7, and blank spacers were needed.