Click Here To View Another Inspection


Inspection #: 617823
Inspection Type: Plumbing Rough
Inspector: E.Wood
Result: Correction
Comment: Plumbing rough-in Approved, OK to cover. See corrections. The existing plumbing vent that needs support can be looked at on final above the ceiling grid.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/6/2020CorrectedPlumbRgh14CommentsSee Inspectors CommentsAt the point in the existing venting where the new work (venting) will tie in.Per the 2012 UPC Table 313.1 Hangers and Supports, hubless cast iron, horizontal support to be every other joint, unless over 4' then support within 18" of each joint. Existing piping is well over 4' and has only 1 support.