Inspection #: 616660
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: Equipment required to be in place and connected for inspection. Provide Installation instructions for equipment allowing cord to be used and not permanently connected. Plans show new panel, new panel not installed. Panel schedule incomplete. Ready access for GFCI protection required throughout. Ensure GFCI protection is provided for kitchen areas for other than dwelling units per 210.8 (B) (2) and local amendment.