Inspection #: 615929
Inspection Type: Electrical Rough
Inspector: M.Green
Result: Partial
Comment: Two of three corrections from 7/20/2020 resolved. Conditional electrical final approved until 8/21/2020 to resolve remaining item below. OK for tenant to move in and begin business.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/21/2020Transfer01See inspection comments Existing panels Mech 1 and Mech 2.Drawings show 20KA + of available fault current. 10K rated breakers installed. Engineer's email states that panel Mech 2 motor load will permit series rating. Email indicates that panel Mech 1 does not meet NEC 240.86 criteria for series rating due to motor load. Available fault current at Mech 1 needs to be resolved.