| Date | Status | Code | Description | Ref | Location | Comments |
| 6/16/2020 | Transfer | Correct Below | * | | All 17 Electrical Rooms | Verify motion sensor switch turns on manually, but does not turn off automatically. 110.26(D) requires that illumination at indoor electrical panels cannot be by automatic means only.
Contractor states that the control device automatic shut-off cannot be overridden. A complete manual override is required. |
| 6/16/2020 | Corrected | Correct Below | * | | All 17 Units Panels | Update panel schedules |