Inspection #: 615864
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Requested by: Jeremey Fholer 9074207640 visionelectricak@outlook.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/16/2020TransferCorrect Below* All 17 Electrical RoomsVerify motion sensor switch turns on manually, but does not turn off automatically. 110.26(D) requires that illumination at indoor electrical panels cannot be by automatic means only. Contractor states that the control device automatic shut-off cannot be overridden. A complete manual override is required.
6/16/2020CorrectedCorrect Below* All 17 Units PanelsUpdate panel schedules