Inspection #: 614738
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: anytime works Thank you! Requested by: Jon Hounchell 907-229-9808 jhounchell@alcanelectric.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/20/2020TransferCorrect Below* Upstairs panels Mech 1 and Mech 2 existing condition.Panels above are shown on drawings as having available fault current of over 20KA. 10K branch circuit breakers installed. Breakers may not series rate because of motor loads in panels. Engineer needs to investigate.
7/20/2020TransferCorrect Below* Panel 1LSCorrect panel schedules, post floor plan for office furniture.
7/20/2020TransferCorrect Below* Panel 1LS 3-pole breakers or handle ties required for office furniture multi-wire branch circuits.