Inspection #: 611638
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Boiler / circ pump replacement. Field change order required for deviations from approved drawings as noted below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/25/2020 Correct Below* Circ pump circuit.Drawings show (3) 3-ph. circ. pumps on a 15A circuit. Installation is (4) circ. pumps on a 20A circuit.
9/25/2020 Correct Below* Boiler OCPD.Drawings show 15A breakers. Boiler data plate shows 12A max load. 20A breakers installed. No clear instructions as to proper OCPD.