| Date | Status | Code | Description | Ref | Location | Comments |
| 9/25/2020 | | Correct Below | * | | Circ pump circuit. | Drawings show (3) 3-ph. circ. pumps on a 15A circuit. Installation is (4) circ. pumps on a 20A circuit. |
| 9/25/2020 | | Correct Below | * | | Boiler OCPD. | Drawings show 15A breakers. Boiler data plate shows 12A max load. 20A breakers installed. No clear instructions as to proper OCPD. |