| Date | Status | Code | Description | Ref | Location | Comments |
| 4/28/2020 | Transfer | Correct Below | * | | Exhaust fan #1. | Does not appear to have a listing mark. Listing mark required to be on the product. Also, 4.5A FLA motor may be too small for a 20A breaker. |
| 4/28/2020 | Corrected | Correct Below | * | | Panels. | Circuits shown on dwgs as supplied from panel 1LB. Actual source of supply is panel 1LA due to lack of space in panel. Engineer needs to include this change in field change order. |
| 4/28/2020 | Corrected | Correct Below | * | | Exhaust fan #1. | Shown on dwgs as a 30A, 1-pole circuit. Installed unit is supplied by a 3-pole, 20A circuit and controlled by a VFD. Engineer needs to submit field change order. |