Inspection #: 609260
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: (2) items from 4/28/2020 resolved; electrical engineer has provided Field Change Orders. Unlisted exhaust fan #1: Motor is a UL recognized component (but not listed). Flexible duct with controls is unlisted but claimed to be low voltage operated. VFD controlling motor and possibly supplying control power to flexible duct. It MAY be possible to approve this assembly of components without an actual NRTL listing or NRTL field evaluation if: 1. All voltage to the flexible duct is from a class 2 power source. 2. There is no line voltage powering anything other than the VFD and motor. Verify that the breaker supplying exhaust fan #1 has been changed to 15A per engineer's Field Change Order. Call Mike after receiving this report: 317-6980.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/28/2020TransferCorrect Below* Exhaust fan #1.Does not appear to have a listing mark. Listing mark required to be on the product. Also, 4.5A FLA motor may be too small for a 20A breaker.
4/28/2020CorrectedCorrect Below* Panels.Circuits shown on dwgs as supplied from panel 1LB. Actual source of supply is panel 1LA due to lack of space in panel. Engineer needs to include this change in field change order.
4/28/2020CorrectedCorrect Below* Exhaust fan #1.Shown on dwgs as a 30A, 1-pole circuit. Installed unit is supplied by a 3-pole, 20A circuit and controlled by a VFD. Engineer needs to submit field change order.