Inspection #: 608431
Inspection Type: Electrical Rough
Inspector: E.Widman
Result: Correction
Comment: Inspection is for gate B-8 bridge. Corrections. Note: update electrical permit to include each electrical contractor. Seperate contractors responsible for parts of work.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/23/2020Transfer01See inspection comments Physical protection required for conduit entries containing #4 or larger conductors.  
4/23/2020Transfer01See inspection comments Flexible cord terminations at splice from building wire to bridge and at power distribution box. Terminations approved for use required at flexible cord stranded conductors.
4/23/2020Transfer01See inspection comments exterior interconnection.Flexible cord not permitted to be concealed within building.