| Date | Status | Code | Description | Ref | Location | Comments |
| 1/4/2021 | Transfer | FNLSG | Final Structural Other | Please correct the following: | Exterior housekeeping pad for electrical gear. | 1) No inspection was made of reinforcement by the MOA prior to placing concrete.
2) Slab thickness is indicated on plans to require 10" thickness, slab was poured to 4" thickness.
3) Special Inspection for reinforcement of slab and of retro-fit anchor bolts was not provided. |