Inspection #: 605272
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/27/2020 Correct Below* New sink/prep area.Verify readily accessible GFCI protection is provided for receptacles in this location. Not tested while onsite, not certain of protection method (Breaker location) and ability to reset receptacles.
2/27/2020 Correct Below* Panel schedule. Update panel schedule for new circuits related to work.
2/27/2020 Correct Below* Above ceiling. Lighting outlet required at equipment requiring servicing.
2/27/2020 Correct Below*  Flexible cord not permitted to be concealed in building. Chapter 3 wiring method required.
2/27/2020 Correct Below* Provide installation instructions for equipment.  
2/27/2020 Correct Below* New counter area. Provide MOA stamped reviewed plans for inspections. Plans provided do not appear to include new cooler.