Inspection #: 598725
Inspection Type: Ceiling / Act
Inspector: P.Calhoun
Result: Correction
Comment: Requested by: Jimmy Houston 9074404992 jhouston@rhcak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/21/2020 ACTCSee Inspector commentsInspector comments Provide approved design criteria for use of concealed spline materials in leu of #12 wire to support tees.
1/21/2020 ACTCSee Inspector commentsInspector comments Wires supporting ceiling grid shall not be more than 1" in 6" out of plumb.