Date | Status | Code | Description | Ref | Location | Comments |
9/26/2019 | Corrected | PlumbFinal6 | ADA Requirements | Fixtures are not installed per ADA requirements-Per ANSI A1171.1 code | public lavs | ASSE 1070 mix valves required serving hot side. |
9/26/2019 | Corrected | PlumbFinal6 | ADA Requirements | Fixtures are not installed per ADA requirements-Per ANSI A1171.1 code | Public/ADA WCs | Flush handle shall be located on open side of room/stall & seat shall be of open front style. |
9/26/2019 | Corrected | PlumbFinal17 | Backflow Preventer Required | An approved backflow preventer is required-UPC 602.2 | Laundry | Provide documentation commercial clothes washing machines have backflow prevention precautions regarding chemical injection. |
9/26/2019 | Corrected | PlumbFinal2 | Caulk Fixtures | Fixture(s) shall be caulked-407.2 | WC/lav/urinal | Caulk required where fixture/countertop meets wall/floor. |
9/26/2019 | Corrected | PlumbFinal13 | Reversed Water | Hot and cold water is reversed-UPC 415.0 | Multiple shower valves | |
9/26/2019 | Corrected | PlumbFinal1 | WaterTempTub/Shower | <em>Tub/shower water temperature is required to be between 110-120 degress fahreneit- UPC 418 and local amendment 419</em> | Multiple shower valves | |