Inspection #: 597059
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/3/2020 Correct Below*  Readily accessible GFCI protection for other circuits in area. Letter provided for previous area is noted for C19-1731, does not include this permit.
1/3/2020 Correct Below* Lower level electrical room.Foreign system piping not permitted in equipment space. Reference 110.26 (E)(1)(a). Foreign systems required to be above dedicated equipment space. Defined as 6' above equipment, or to structural ceiling.