| Date | Status | Code | Description | Ref | Location | Comments |
| 1/3/2020 | Transfer | Correct Below | * | | | Readily accessible GFCI protection for other circuits in area. Letter provided for previous area is noted for C19-1731, does not include this permit. |
| 1/3/2020 | Transfer | Correct Below | * | | Lower level electrical room. | Foreign system piping not permitted in equipment space. Reference 110.26 (E)(1)(a). Foreign systems required to be above dedicated equipment space. Defined as 6' above equipment, or to structural ceiling. |