Inspection #: 597010
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final conditionally approved for use until 1/17/20. Complete electrical final approval pending resolution of noted corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/3/2020TransferCorrect Below*  Readily accessible GFCI protection for other circuits in area. Letter provided for previous area is noted for C19-1731, does not include this permit.
1/3/2020TransferCorrect Below* Lower level electrical room.Foreign system piping not permitted in equipment space. Reference 110.26 (E)(1)(a). Foreign systems required to be above dedicated equipment space. Defined as 6' above equipment, or to structural ceiling.