Inspection #: 596637
Inspection Type: Fire Alarm Final
Inspector: B.Meinhardt
Result: Partial
Comment: Inspection to test the in unit audible devices. Requested by: Erik Bardauskas 907-360-3666 ebardauskas@yukonfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/26/2021Transferfirealarm11Fire Alarm approved CCOFire Alarm approved for CCO Fire Alarm approved for CCO till April 30, 2021
3/26/2021TransferFirealarm14Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Provide As-Built plans to the MOA plans to show new locations of horn strobes over the doors to the units.
3/26/2021TransferFirealarm15Correction(s) #2<div>Correct the following item(s):</div><div><br></div> Install breaker lock on electrical breakers serving fire alarm system, label electrical panel for FACP Breaker, label FACP where the breaker location is located.&nbsp;
3/26/2021TransferFirealarm16Correction(s) #3<div>Correct the following item(s):</div><div><br></div> Post operating instructions at front desk on how to reset fire alarm systems
3/26/2021TransferFirealarm17Correction(s) #4<div>Correct the following item(s):</div><div><br></div> Label front desk annunciator "Dedicated Function Fire Alarm Panel - Room Notification Only"
3/26/2021TransferFirealarm18Correction(s) #5<div>Correct the following item(s):</div><div><br></div> Label new fire alarm panel "Dedicated Function Fire Alarm Panel - Room Notification Only"&nbsp; and&nbsp; &nbsp;"Room Strobe Notification is Supplementary Only per 2010 edition of NFPA 72 Section 18.7"&nbsp; and "Permit F17-1159 and X20-1594 for Audible Upgrade Only"
3/26/2021TransferFirealarm19Correction(s) #6<div>Correct the following item(s):</div><div><br></div> Provide plans next to new FACP panel.