| Date | Status | Code | Description | Ref | Location | Comments |
| 3/26/2021 | Transfer | firealarm11 | Fire Alarm approved CCO | Fire Alarm approved for CCO | | Fire Alarm approved for CCO till April 30, 2021 |
| 3/26/2021 | Transfer | Firealarm14 | Correction(s) #1 | <div>Correct the following item(s):</div><div><br></div> | | Provide As-Built plans to the MOA plans to show new locations of horn strobes over the doors to the units. |
| 3/26/2021 | Transfer | Firealarm15 | Correction(s) #2 | <div>Correct the following item(s):</div><div><br></div> | | Install breaker lock on electrical breakers serving fire alarm system, label electrical panel for FACP Breaker, label FACP where the breaker location is located. |
| 3/26/2021 | Transfer | Firealarm16 | Correction(s) #3 | <div>Correct the following item(s):</div><div><br></div> | | Post operating instructions at front desk on how to reset fire alarm systems |
| 3/26/2021 | Transfer | Firealarm17 | Correction(s) #4 | <div>Correct the following item(s):</div><div><br></div> | | Label front desk annunciator "Dedicated Function Fire Alarm Panel - Room Notification Only" |
| 3/26/2021 | Transfer | Firealarm18 | Correction(s) #5 | <div>Correct the following item(s):</div><div><br></div> | | Label new fire alarm panel "Dedicated Function Fire Alarm Panel - Room Notification Only" and "Room Strobe Notification is Supplementary Only per 2010 edition of NFPA 72 Section 18.7" and "Permit F17-1159 and X20-1594 for Audible Upgrade Only" |
| 3/26/2021 | Transfer | Firealarm19 | Correction(s) #6 | <div>Correct the following item(s):</div><div><br></div> | | Provide plans next to new FACP panel. |