| Date | Status | Code | Description | Ref | Location | Comments |
| 12/30/2019 | Transfer | Correct Below | * | | Lower level electrical room. | Foreign system piping not permitted in equipment space. Reference 110.26 (E)(1)(a). Foreign systems required to be above dedicated equipment space. Defined as 6' above equipment, or to structural ceiling. |
| 12/24/2019 | Transfer | Correct Below | * | | Readily accessible GFCI protection for other circuits in area. Letter provided for previous area is noted for C19-1731, does not include this permit. | |
| 12/24/2019 | Corrected | Correct Below | * | | Hot water tower. | Cord subject to physical damage at receptacle. Cabinet blocking receptacles. Relocate receptacle. |
| 12/24/2019 | Corrected | Correct Below | * | | 120 volt receptacles. Readily accessible GFCI protection for all in area. | |