Inspection #: 596353
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Correction
Comment: See corrections.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/30/2019TransferCorrect Below* Lower level electrical room. Foreign system piping not permitted in equipment space. Reference 110.26 (E)(1)(a). Foreign systems required to be above dedicated equipment space. Defined as 6' above equipment, or to structural ceiling.
12/24/2019TransferCorrect Below* Readily accessible GFCI protection for other circuits in area. Letter provided for previous area is noted for C19-1731, does not include this permit.  
12/24/2019CorrectedCorrect Below* Hot water tower. Cord subject to physical damage at receptacle. Cabinet blocking receptacles. Relocate receptacle.
12/24/2019CorrectedCorrect Below* 120 volt receptacles. Readily accessible GFCI protection for all in area.  