Inspection #: 594151
Inspection Type: Other - Mechanical
Inspector: K.Hanson
Result: Partial
Comment: Partial Mechanical Rough - Approved To include final grease duct connection weld & 2nd layer of fire wrap serving 90-transition piece, OK for 1st layer on double 45 section. NOTE 1: 2nd CO door required, both CO doors shall be rated for 1500f, will inspect after installation. NOTE 2: If MAU is over 400#s, deferred submittals required.