Inspection #: 592542
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/29/2020TransferCorrect Below* MDPLabeling for the series ratings. 2017 NEC 240.86 (A) (B). 110.22 (C)
6/29/2020TransferCorrect Below* Service and MDPAFC 68,780 at service. What is AFC at MDP? MDP had 65k rated. What is AFC at Branch circuit panels? Breakers rated 10K? What is the AFC at RTU units? RTU units rated at 5k.
6/29/2020TransferCorrect Below* Front and Central Cashier areasCord and plug system for powering receptacles. Does not appear to be a listed system. As well as some of the receptacles are not wired correctly showing open ground.
6/29/2020TransferCorrect Below* SE corner, Front, Central areasReceptacles have no power
6/29/2020TransferCorrect Below* RooftopExhaust fan on rooftop does not have a disconnect in line of sight.
6/29/2020TransferCorrect Below* Back storage area and loading dockEmergency lights not working
6/29/2020TransferCorrect Below* Back Hallway near restroomsExit signs not working, and emergency light outside exit door.
6/29/2020TransferCorrect Below* Break roomGFI protection required for receptacles within 6 ft of the sink.
6/29/2020TransferCorrect Below* Loading dockInstall a box, and cover plates, for security lighting.
6/29/2020TransferCorrect Below* GutterNorth End of Gutter appears to have more than 30 current carrying conductors. 2017 NEC 366.22 (A)
6/29/2020TransferCorrect Below* MDPInstall panel schedules, Label for RTU7, and blank spacers were needed.