| Date | Status | Code | Description | Ref | Location | Comments |
| 6/29/2020 | Transfer | Correct Below | * | | MDP | Labeling for the series ratings. 2017 NEC 240.86 (A) (B). 110.22 (C) |
| 6/29/2020 | Transfer | Correct Below | * | | Service and MDP | AFC 68,780 at service. What is AFC at MDP? MDP had 65k rated. What is AFC at Branch circuit panels? Breakers rated 10K? What is the AFC at RTU units? RTU units rated at 5k. |
| 6/29/2020 | Transfer | Correct Below | * | | Front and Central Cashier areas | Cord and plug system for powering receptacles. Does not appear to be a listed system. As well as some of the receptacles are not wired correctly showing open ground. |
| 6/29/2020 | Transfer | Correct Below | * | | SE corner, Front, Central areas | Receptacles have no power |
| 6/29/2020 | Transfer | Correct Below | * | | Rooftop | Exhaust fan on rooftop does not have a disconnect in line of sight. |
| 6/29/2020 | Transfer | Correct Below | * | | Back storage area and loading dock | Emergency lights not working |
| 6/29/2020 | Transfer | Correct Below | * | | Back Hallway near restrooms | Exit signs not working, and emergency light outside exit door. |
| 6/29/2020 | Transfer | Correct Below | * | | Break room | GFI protection required for receptacles within 6 ft of the sink. |
| 6/29/2020 | Transfer | Correct Below | * | | Loading dock | Install a box, and cover plates, for security lighting. |
| 6/29/2020 | Transfer | Correct Below | * | | Gutter | North End of Gutter appears to have more than 30 current carrying conductors. 2017 NEC 366.22 (A) |
| 6/29/2020 | Transfer | Correct Below | * | | MDP | Install panel schedules, Label for RTU7, and blank spacers were needed. |