| Date | Status | Code | Description | Ref | Location | Comments |
| 12/30/2019 | | firealarm13 | Please correct the following | Please correct the following: | | Horns at 508, 607, 708, 910, and 1004 did not activate at test. Horn at unit 1508 drifted in and out. Note: Only 1004 horn recorded to the panel a trouble. |